How to do a system check?

Conducting a 1:1 test is the simplest way to execute a self test.

 1. Begin by connecting the clips as follows:

- Connect H1 to X1

- Connect H2 to X2

- Connect H3 to X3

- Connect H0 to X0

2. Turn on the power to the system.

3. Navigate to the settings menu and select the configuration labeled Yn:Yn, with the parameters set to 0 and 100V.

4. Once configured, press the "Go ABC" button to initiate the test.

5. After the test is complete, you should observe results indicating a reading of approximately 1.0000 on each phase.

Before powering on the test set, it is essential to conduct a visual inspection of your test leads. Check for any signs of damage, including issues with wire insulation, clips, and clip insulators.