Conducting a 1:1 test is the simplest way to execute a self test.
1. Begin by connecting the clips as follows:
- Connect H1 to X1
- Connect H2 to X2
- Connect H3 to X3
- Connect H0 to X0
2. Turn on the power to the system.
3. Navigate to the settings menu and select the configuration labeled Yn:Yn, with the parameters set to 0 and 100V.
4. Once configured, press the "Go ABC" button to initiate the test.
5. After the test is complete, you should observe results indicating a reading of approximately 1.0000 on each phase.
Before powering on the test set, it is essential to conduct a visual inspection of your test leads. Check for any signs of damage, including issues with wire insulation, clips, and clip insulators.